DN-6862:C1. 8/1/2011 — Page 1 of 4 ACS Series Annunciators ONYX ® Series ACM/AEM-24AT, ACM/AEM-48A DN-6862:C1. D-95 Annunciator Control Systems General The ONYX® Series ACS Annunciators provide a modular line of products for annunciation and control of the NOTIFIER ONYX® Series Intelligent Fire Alarm Control Panels, Network Control Annunciators, and NOTIFIER’s legacy addressable panels.

Official Yamaha Online Manual Site. Don't settle for anything less - help protect your investment by using Genuine Yamaha manuals. Yamaha atv owners manual download. The Yamaha Owner's Manual Section offers the ability to view Owner's Manuals for many past Yamaha models. -- Select Product Line --, ATV, Motorcycle.

The ACS line provides arrays of LEDs to indicate point status and, in some versions, switches to control the state of output circuits. These ACS units use a serial interface and may be located at distances of up to 6,000 feet (1,828.8 meters) from the panel. Features. Speaker control mode for use with XPIQ and the following panels: NFS2-3030, NFS2-640, NFS-320(C) and NFS- 320SYS. Enables the ACS to control operation of groups of multi-channels mapped to groups of multi-speakers. Compatible with existing annunciators.

Color-programmable LEDs. On-board end-of-line resistors can be enabled/disabled by setting a switch. Alarm/Circuit On and Trouble LED per-point thxoption or more dense Alarm-only option.

Touch-pad control switch option for remote control of sys- tem relays; or silence, reset, and evacuate. LEDs may be programmed to display status of indicating circuits or control relays as well as system status condi- tions. System Trouble LED indicator. On-Line/Power LED indicator. Alarm and trouble resound with flash of new conditions. Local sounder for both alarm and trouble conditions with silence/acknowledge button (program options).

Notifier manual

Notifier Xpiq Manual

May be powered by 24 VDC from the panel or by remote power supplies. Microprocessor-controlled electronics, fully supervised. Slip-in custom labels, lettered with standard typewriter or LabelEase program. Plug-in terminal blocks for ease of installation and service.

Construction The ACS modules are provided in two basic controller mod- ules, each with its expander module. The ACM-24AT provides 24 annunciation and control points per module, each with a red, green, or yellow Alarm/Circuit On LED, a yellow Trouble LED, and a touch-key switch. The ACM-48A provides 48 annunciation points per module, each with a red, green, or yel- low Alarm/Circuit On LED (for annunciating control relays, the LED indicates ON/OFF). On the ACM-24AT, each LED point is individually color-pro- grammable. On ACM-48A, each column of 24 LED points can be color-configured using a DIP switch.

Notifier

Temperature and humidity ranges: This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F); and at a relative humidity (noncondensing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humid- ity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15°C to 27°C (60°F to 80°F). Installation The ACS Series annunciator and control subsystems use modular hardware assemblies which allow the custom configu- ration of the annunciator panel to fit the individual job require- ments. Standard backboxes and mounting hardware schemes, includ- ing special remote cabinets, allow the annunciators to be con- structed and configured with other system components.

When used with the NFS2-3030, NFS2-640, NFS-320 or leg- acy panels, the ACS modules can be used for manual selec- tion of speaker and telephone circuits. In this application, they are typically mounted in the main control near the microphone and telephone handset. For remote annunciation applications, the modules are typi- cally mounted in special ABF or ABS boxes. Control switch key locks (AKS-1B) are available. Communication between the ACS Series annunciators and the host Fire Alarm Control Panel is made through an EIA-485 multi-drop loop, eliminating the need for costly wiring schemes. Four wires are required, two for the EIA-485 com- munications (twisted pair), and two for 24 VDC regulated power.

Retrofit of ACS Series annunciators into existing systems is easily accomplished. Software may require upgrading, and some legacy panels may require an interface board.

All field-wiring terminations use removable, compression-type terminal blocks for ease of installation, wiring, and circuit test- ing. ACM/AEM-24AT ACM/AEM-48A 6862at24.wmf 6862a48.wmf.