Long Description The MR-2351-LD-RA is a single loop fire alarm control unit that supports up to 126 points. The system can be expanded to a three loop 378 point system with the addition of an ALC-252 Dual Loop Controller Module. The MR-2351-LD-RA is equipped with a two line by 20 character back-lit LCD display, numerical keypad, an integrated UDACT/Digital Communicator and space for up to 64 zones of LED annunciation (requires optional RAX-332 modules). The LCD display allows for 32 characters to be configured for user defined messages. In addition the MR-2350 Series family also includes remote LED and LCD annunciators.
The MR-2351-LD-RA is ideal for both new and retrofit applications. Designed for small to medium commercial, institutional and industrial occupancies, these panels are powerful enough to meet today’s installation demands. The MR-2351-LD-RA is configurable by the keypad for onsite programming or by a PC for both onsite and remote programming. Easy to install and simple to operate and configure, the MR-2351-LD-RA enables the installer to configure the system to meet their specific requirements. The MR-2351-LD-RA is equipped with a 5.5 Amp power supply, auxiliary resettable smoke power supply (300mA max.), an interface for a Remote Trouble Indicator (SRTI-200) and an RS-485 interface for remote LCD and LED annunciators. The MR-2351-LD-RA comes complete with a red door, black enclosure, durable CAT-30 lock and key and space to mount up to 18 AH batteries. Comes With.
Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual • Programming reference sheets • Fire-Lite Equipment. The UDACT-2 program will need to do a Auto Populate, which takes the ACS point. Check the programming manual for number of ACS board.
Two Line LCD Display. 1 Intelligent Loop (126 Devices). 4 Indicating Circuits(1.7 Amps) Class B (Style Y).
2 Line UDACT Digital Communicator & Modem. Supports Multiplexed LCD & LED Remote Annunciation. Alarm & Event Logs. 5 Amp Power Supply (Signal & Aux Supply). Configurable Via Front Panel, Laptop or Remote Dial Up.
Provision to expand to 378 points (Requires ALC-252). Provision to add two RAX-332. Red Door and Black Enclosure. Features. Single intelligent SLC Loop that supports 126 points.
UDACT-2 Programming and downloading for NFS-3030 Adding a U-DACT2 to an existing NFS-3030 database within VeriFire Tools OverView: You will need the newer VireFire Tools to load the UDACT-2 'License version' no way around it. The UDACT-2 does not just program itself, you will need to work a little Each point within the system 'L1D1,L4M150' is assigned to a point Within the ACS mapping The UDACT-2 program will need to do a Auto Populate, which takes the ACS point mapping and populates the UDACT/CENTRAL STATION INFO once this is done you will need to Load the UDACT board. Open database (NFS-3030). 'ADD NODE' ' UDACT WILL BE THE SAME ADDRESS AS PANEL' Under Edit Session you are going to add another node, this node is a UDACT2 3.
Settings within the panels ACS Mapping a. Make one of the ACS board addresses UDACT (address 1 is ok) The first address will give you 64-8=56 points to assign points to 'IE L1M1' 'If VeriFire Tools is working right it will auto assign points to the ACS board/ACS points' b. You will ussally need to add ACS boards as '64 pt ACS' so all the devices/points can be assigned to ACS points. As you add '64 pt ACS' to ACS mapping 'Board Type' may or may not be auto assigned. If not auto assigned you will need to manually add the 'Function' and 'Source' IE.
'Monitor' 'L1M1' If auto assign is working add '64 pt ACS' board types until all points are assigned Check the programming manual for number of ACS board addresses needed c. Manually assigning ACS point info, can be done, quite annoying, if it is not going to auto assign you will need to manully, good luck 4. Settings within UDACT - Generasl Settings a. Reporting type - point transmit/receive b.
Add dialer info, format CID, account, phone number c. ACS Addressing - start 1 - end 'as needed' IE 2 thru 32 this will need to match the 'ACS Board' settings in ACS mapping Maxium of 32 addresses will give you 2000 points to use. Remember the 3030 has 3030 point max. Zone and point assignment- 'Auto Populate' this will take the ACS point info and assign it a Central Station point. Last Thing: Run Report select node- UDACT Select type- Central Station Check what you did, also clear report and send to CS - DOWNLOAD the UDACT a. Plug your USB cable into he UDACT, hit 'Local Network' b.
Udact Trouble On Fire Panel
Switch switch 2 on udact board 'SWITCH 2 ON/OFF TO LOAD' c. Turn switch 2.